Note that ISARSI accepts only one IXL client at a time.
To increase this limitation you need to have the PrDK product and change some source files:
- in ETCP, increase the ETCP_SRV_MAX_CLT_QUEUE macro in detc0mai.c
Example with NT target to manage 10 IXL clients with ETCP driver:
- Create ETCP.INI if it does not exist.
- Add in ETCP.INI the following section :
[APP]
NbIxlClt=10Under VxWorks, use putEnv("ETCP_NBIXLCLT=10")
Under OS9, use setenv("ETCP_NBIXLCLT=10")
See also the FAQ: "Increasing Max. number of Resources", you should multiplie parameters of IXD and ETCP by the number of IXL clients you have.
add in ISAVM.ini in the following section:
[SRV]
CnxNbr=10
Under VxWorks, use putEnv("ISAVM_SRV_CNXNBR=10)
Under OS9, use setenv("ISAVM_SRV_CNXNBR=10)
To be noted also in this case, the number of answers / cycle of the Virtual machine can be parameterized with SRV - MAXSCAN parameter.